1.5mm 2.5mm 4mm 6mm 10mm wire cable
0.6/1kv underground cable xlpe insulated power cable
Jointly developed by China secience and technology university and our works
Application characteristics:
1)Ratedal temperature of conductor is 105°c
2)AC voltage test
The test should be carried out on the complete drum of cable. when the environmental temperature is 20±15°c,apply AC 3.5kv for 5 minutes.the insulation should not break drown during test.
BV in stock
The following specifications are in stock,small quantity is welcome.
Name | Usage | Specification |
450/750V Copper conductor PVC insulated rigid cable (electrical wire)
| Building and construction, instrument | BV 1.5mm² |
BV 2.5mm² | ||
BV 4mm² | ||
BV 6mm² | ||
BV 10mm² | ||
BV 16mm² | ||
BV 25mm² | ||
BV 35mm² | ||
BV 50mm² | ||
BV 70mm² | ||
BV 95mm² | ||
BV 120mm² | ||
BV 150mm² | ||
BV 185mm² |
2.5mm pvc cable
Reference Standard: The product is manufactured according to the stand of GB12706 or IEC,BS,DIN and ICEA upon request. Applications: The product is suitable for power installation fixed wiring or flexible connection for electrical appliances with rated voltage up to and including 450/750V respectively
Operating characteristics:
Rated power-frequency voltage Uo/U:450/750V; 300/500V and 300/300V
Max. permissible continuous operating temperature of conductor:
227 IEC 07 (BV-90)------------90oC 227 IEC 08 (BV-90)------------90oC
For other types------------------70oC
The ambient temperature under installation should not below 0
The bending radius of cable:
D≤25mm----------≥4D
D>25mm-----------≥6D
(D-diameter of the cable)
Type | Name |
227 IEC 01 (BV) | Single-core non-sheathed cable with solid conductor for general purposes |
227 IEC 02 (RV) | Single-core non-sheathed cable with flexible conductor for general purposes |
227 IEC 05 (BV) | Single-core non-sheathed cable with solid conductor for internal wiring for a conductor temperature of 70oC |
227 IEC 06 (RV) | Single-core non-sheathed cable with flexible conductor for internal wiring for a conductor temperature of 70oC |
227 IEC 07 (BV-90) | Single-core non-sheathed cable with solid conductor for internal wiring for a conductor temperature of 90oC |
227 IEC 08 (RV-90) | Single-core non-sheathed cable with flexible conductor for internal wiring for a conductor temperature of 90oC |
227 IEC 10 (BVV) | Light PVC sheathed cable |
227 IEC 42 (RVB) | Flat non-sheathed flexible cable |
227 IEC 52 (RVV) | Light PVC sheathed flexible cable |
227 IEC 53 (RVV) | Ordinary PVC sheathed flexible cable |
227 IEC 74 (RVVYP) | Oil-proof PVC sheathed, screened flexible cable |
227 IEC 75 (RVVY) | Oil-proof PVC sheathed, non screened flexible cable |
Type | Rated voltage V | No. of cores | Nominal cross-sectional area of conductor (mm2) | Standards |
227 IEC 01 (BV) | 450/750 | 1 | 1.5~400 | GB5023-1997 IEC60227-1997 |
227 IEC 02 (RV) | 450/750 | 1 | 1.5~240 | |
227 IEC 05 (BV) | 300/500 | 1 | 0.5~1 | |
227 IEC 06 (RV) | 300/500 | 1 | 0.5~1 | |
227 IEC 07 (BV-90) | 300/500 | 1 | 0.5~2.5 | |
227 IEC 08 (RV-90) | 300/500 | 1 | 0.5~2.5 | |
227 IEC 10 (BVV) | 300/500 | 2,3,4,5 | 1.5~35 | |
227 IEC 42 (RVB) | 300/300 | 2 | 0.5~0.75 | |
227 IEC 52 (RVV) | 300/300 | 2,3 | 0.5~0.75 | |
227 IEC 53 (RVV) | 300/500 | 2~24 | 0.75~6 | |
227 IEC 74 (RVVYP) | 300/500 | 2~26 | 0.5~2.5 | |
227 IEC 75 (RVVY) | 300/500 | 2~26 | 0.5~2.5 |